IEC 61000-3-2:2018 is also available as
IEC 61000-3-2:2018 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.
IEC 61000-3-2:2018 deals with the limitation of harmonic currents injected into the public supply system. It specifies limits of harmonic components of the input current which can be produced by equipment tested under specified conditions. It is applicable to electrical and electronic equipment having a rated input current up to and including 16 A per phase, and intended to be connected to public low‑voltage distribution systems. Arc welding equipment which is not professional equipment, with a rated input current up to and including 16 A per phase, is included in this document. Arc welding equipment intended for professional use, as specified in IEC 60974-1, is excluded from this document and can be subject to installation restrictions as indicated in IEC 61000-3-12. The tests according to this document are type tests. For systems with nominal voltages less than but not equal to 220 V (line-to-neutral), the limits have not yet been considered.
This fifth edition cancels and replaces the fourth edition published in 2014. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) an update of the emission limits for lighting equipment with a rated power ≤ 25 W to take into account new types of lighting equipment;
b) the addition of a threshold of 5 W under which no emission limits apply to all lighting equipment;
c) the modification of the requirements applying to the dimmers when operating non‑incandescent lamps;
d) the addition of test conditions for digital load side transmission control devices;
e) the removal of the use of reference lamps and reference ballasts for the tests of lighting equipment;
f) the simplification and clarification of the terminology used for lighting equipment;
g) the classification of professional luminaires for stage lighting and studios under Class A;
h) a clarification about the classification of emergency lighting equipment;
i) a clarification for lighting equipment including one control module with an active input power ≤ 2 W;
j) an update of the test conditions for television receivers;
k) an update of the test conditions for induction hobs, taking also into account the other types of cooking appliances;
l) for consistency with IEC 61000-3-12, a change of the scope of IEC 61000-3-2 from equipment with an input current ≤ 16 A to equipment with a rated input current ≤ 16 A.
تتناول المواصفة القياسية IEC 61000-3-2:2018 الحد من التيارات التوافقية التي يتم حقنها في نظام الإمداد العام. وهي تحدد حدود المكونات التوافقية لتيار الإدخال التي يمكن إنتاجها بواسطة المعدات التي تم اختبارها في ظل ظروف محددة. تنطبق هذه المواصفة القياسية على المعدات الكهربائية والإلكترونية التي لها تيار دخل مقدر يصل إلى 16 أمبير لكل مرحلة، والمخصصة لتوصيلها بأنظمة التوزيع العامة ذات الجهد المنخفض. معدات اللحام بالقوس الكهربائي التي ليست معدات احترافية، مع تيار دخل مقدر يصل إلى 16 أمبير لكل مرحلة، متضمنة في هذه الوثيقة. يتم استبعاد معدات اللحام بالقوس الكهربائي المخصصة للاستخدام المهني، كما هو محدد في المواصفة القياسية IEC 60974-1، من هذه الوثيقة ويمكن أن تخضع لقيود التثبيت كما هو موضح في المواصفة القياسية IEC 61000-3-12. الاختبارات وفقًا لهذه الوثيقة هي اختبارات نوعية. بالنسبة للأنظمة ذات الفولتية الاسمية الأقل من 220 فولت (من الخط إلى الحياد) ولكن لا تساويها، لم يتم النظر في الحدود بعد.